Skip to content
S.K Trading & Co.Valves, Pipes & Fittings Stockist
Valves · Regulating

Pressure reducing valve

Brings line pressure down to a set, steady value.

Screwed pressure reducing valve with brass spring housing

1 / 3

1 / 3

Screwed pressure reducing valve with brass spring housing

Screwed pressure reducing valve with brass spring housing

Also called: PRV, pressure reducer, pressure regulating valve, water pressure reducing valve, steam PRV

  • Since 2019
  • GST registered
  • MSME (Udyam) registered
  • ISO 9001:2015 certified

Delivery across Mumbai, Thane and Navi Mumbai; supply all over India.

What it is

A pressure reducing valve (PRV) takes a higher, changing inlet pressure and gives a lower, steady outlet pressure. A spring set by an adjusting screw balances the outlet pressure acting on a diaphragm or piston: when the outlet pressure drops, the valve opens further, and when it rises, the valve closes down. PRVs protect pipework, fixtures and equipment from too much pressure.

To choose a PRV we need the fluid, the inlet pressure range, the outlet pressure you want, the flow and the line size. A PRV is usually fitted with a strainer before it, isolating valves on both sides, pressure gauges and a bypass.

Types

The common types. Tell us the one your job needs.

Design

  • Direct-actingThe outlet pressure acts straight on a spring-loaded diaphragm or piston. Simple and compact, for small and medium flows.
  • Pilot-operatedA small pilot valve controls the main valve, holding the set pressure closely over a wide range of flows. For large lines and steam.

Service

  • WaterBuildings, high-rise supply zones, fire and process water.
  • SteamBrings boiler pressure down to what the plant needs.
  • Air and gasesCompressed air and gas lines.

Ends

  • ScrewedSmall sizes, usually up to 50 mm.
  • FlangedLarger sizes and steam pressure reducing stations.

Body material

  • Bronze and gunmetalSmall valves for water and air.
  • Cast iron and ductile ironWater and low-pressure steam.
  • Cast steelSteam at higher pressures and temperatures.
  • Stainless steelClean steam, food and chemical service.

Grades and standards

Standards buyers commonly specify. Quote the one in your specification.

EN 1567
Water pressure reducing valves for use in buildings.
ASME B16.34
Pressure–temperature ratings of steel valve bodies.
ASME B16.5 / EN 1092
Flange drilling for flanged valves (Class or PN).
IBR
Steam PRVs on lines under the Indian Boiler Regulations need IBR documents.

Where it is used

Services

  • Domestic and process water
  • Steam
  • Compressed air
  • Fire-fighting water
  • Gases

Industries

  • High-rise buildings
  • Hotels and hospitals
  • Boiler houses
  • Textile, food and pharmaceutical plants
  • Water supply networks

Documents with the order

  • Maker's test certificate supplied where available. Ask when you order.

Common questions

Where should a PRV be fitted?

On a straight run of pipe, after a strainer and an isolating valve, with a pressure gauge on each side and an isolating valve after it. A bypass with a globe valve lets the line keep running while the PRV is serviced.

Can the outlet pressure be adjusted?

Yes. Each PRV has a set range, and the outlet pressure is set with the adjusting screw within that range. Tell us the outlet pressure you want so we offer a valve with the right spring range.

How much can one PRV reduce the pressure?

Each design has a limit on the ratio of inlet to outlet pressure. Where the drop is very large, two PRVs are fitted one after the other. Send the inlet and outlet pressures and the flow and we will check it.

Why does a PRV need a strainer?

Dirt on the seat stops the valve closing fully, so the outlet pressure creeps up. A Y-strainer fitted before the PRV keeps the seat clean.

Does a PRV need a safety valve after it?

On steam, and wherever the equipment after the PRV cannot take the full inlet pressure, a relief or safety valve is fitted after it, in case the PRV fails open.

Do you supply outside Mumbai?

Yes. We deliver across Mumbai, Thane and Navi Mumbai, and supply all over India.

Get an accurate quote, faster

Send these details with your enquiry, or simply send your BOQ. Add the fittings and valves you need to the same list.

Or email your list to admin@sktradingandco.in

  • For valves, tell us

    • Fluid (water, steam, air)
    • Inlet pressure (min and max)
    • Outlet pressure wanted
    • Flow
    • Line size
    • End connection
    • Quantity